Results

Since our total investment in the nation's highway infrastructure amounts in the billions of dollars, it is extremely important that all possible methods applicable to controlling corrosion in existing concrete bridges be developed so that these structures will not deteriorate prematurely. Equally important is developing methods to avoid this costly corrosion problem in all new concrete bridges to be constructed in the future. Accordingly, the research program undertaken in this HPA was divided into two major areas:

To be effective, this research program involved not only the participation of FHWA, but other partners including another federal agency (National Institute of Standards and Technology), some state highway agencies, the academia, and the private industry. The following is a presentation of results or accomplishments achieved to date in these two areas.

A. Corrosion Control in New Concrete Constructions

Given the very harsh service environments that many bridges will be exposed to typically, it is extremely difficult - but not impossible - to build reinforced concrete bridges that would be free of steel reinforcement corrosion. The achievement of this goal would require the adoption of system approach, i.e., using a combination of different measures, such as adequate depth of concrete cover, quality concrete, corrosion inhibitors admixture, and corrosion-resistant reinforcement.

1. Adequate Concrete Cover

It is now widely accepted that, for a concrete structure to be durable in a corrosive environment, it is absolutely necessary to provide an adequate layer of concrete or depth of concrete cover over the first layer of reinforcing steel so that it would not be easy for chloride ions to reach the steel. This adequate depth of cover can be determined by application of Fick's second law of diffusion, which adequately models the intrusion or diffusion of chloride through a porous material such as concrete (17):

(deltaC x/ deltat) = D(delta 2C x/ delta 2X)
(12)

where, C x is the concentration of chloride at depth c at time t, D is the diffusion coefficient of chloride. The solution to this equation for a semi-infinite slab is:

C(X,t) = Co { 1—erf [X / (2 (Dt)½)] }
(13)

which is applicable to concrete structures where the chloride ions enter from one direction, such as concrete bridge decks and piers. Using this relationship, the minimum depth of concrete cover over the reinforcing steel that would be required so that the total amount of chloride ions that will accumulate at the depth of steel will not exceed the corrosion threshold—before a desired service life is reached—can be determined from the measured chloride diffusivity of the selected concrete mix design and the anticipated level of exposure of the structure to deicing salts. Finally, this minimum depth of cover must be incorporated with expected construction tolerances (that accounts for typical construction variance) to achieve a rational depth of cover specification (18). For example, if a minimum concrete cover of 50 mm is required and statistical surveys of the cover on recently built bridge decks show that the cover on a deck typically assumes normal distribution with a standard deviation of approximately 10 mm, then the specified cover must be either 67 mm or 73 mm for 95-percent or 99-percent compliance, respectively.

However, even with adequate concrete cover, corrosion of reinforcement can still occur because, invariably, concrete will crack. In addition, presence of variances in the concrete cover and in the density of the placed concrete across a structure will eventually create corrosion micro-cells (consisting of cathodes and anodes), which drive steel corrosion. Therefore, other supplementary protective measures also need to be adopted in a new construction.

2. Quality Concrete

Recently, there is also a heightened awareness that the quality of concrete is of utmost importance in determining the durability of reinforced concrete bridge members exposed to chlorides and subjected to intermittent wetting. Although concrete is outwardly a dense material, it contains pores; and many of these pores are interconnected to form a network of channels that allows water and oxygen, both important to steel corrosion, to permeate into the concrete. And, as a general rule, low water/cement ratio and good consolidation lead to either a lower number of pores or smaller pores in the concrete, both of which can lead to reduce penneability. In addition, reduced permeability also leads to reduction in the electrical conductivity of the concrete by reducing not only the amount of moisture intrusion but also the amount of chloride ions carried by the moisture into the concrete. A low water/cement ratio also offers higher strength to the concrete, which would extend the time before stresses resulting from steel corrosion cause the concrete to crack. Therefore, mixture proportions must be carefully selected to the keep the water/cement ratio to an absolute minimum.

In addition to making state transportation agencies become aware of the importance of using low water/cement ratio in concrete mixes, some recent FHWA research efforts were aimed at identifying concrete materials that can consistently provide superior performance when used in construction of bridges. These efforts included investigation into how concrete material and mix variables, such as water-cement ratio, air content, coarse aggregate type, fine aggregate type, mineral admixture, and cement type, affect the corrosion behavior of steel (19). The test matrix adopted in this investigation is shown in Table 1.

Table 1. Test Matrix
Variable
Number Type
Cement type 6 Type I-low C3A, Type I-high C3A, Type I-low alkali, Type I-high alkali, calcium aluminate, magnesium phosphate
Mineral admixture 4 Silica flume, Class C fly ash, Class F fly ash, GGBF slag
Coarse aggregate 2 Limestone, quartz
Fine aggregate 2 Glacial sand, quartz sand
Water-cement ratio 3 0.3, 0.4, 0.5
Air content 3 2, 5, 8 percent
Exposure environment
2 Moderate, severe

Because only 30 concrete mix designs were used, which were insufficient to test all the possible combinations of the large number of variables, only weak correlation between corrosion rate or potential and these variables/types were obtained, for both moderate and severe environments. Nevertheless, it was possible to draw some general conclusions, the primary of which was that the corrosion rate of reinforcing steel varies significantly depending on the concrete mix components. Among the variables investigated, water/cement ratio, cement type, mineral admixture, and fine aggregate exhibited the most significant effects on the durability of the concrete. The other factors, such as coarse aggregate and air content, also affect behavior of steel in concrete, but to a lesser extent. The data indicated that the Type I cement (low C3A), quartz fine and coarse aggregates, and silica fume appeared to be the best materials for improving resistance of concrete to deterioration (20).

The use of blended cements might, under certain circumstances, be detrimental because of a reduction in alkalinity in the concrete. However, this adverse effect may be more than offset by the beneficial effects that blended cements can offer, which include a substantial reduction in permeability and also a reduction in conductivity—especially where a reduction in the water-cement ratio is made possible.

In addition, the investigation also attempted to quantify the corrosive conditions fostering concrete bridge deterioration. The effects of environmental variables such as chloride concentration, temperature, and humidity, on the corrosion behavior of reinforcing steel in a typical concrete mix were examined (21). The adopted test matrix is shown in Table 2.

Table 2. Adopted Test Matrix
Chloride Level
kg/m 3 (lb/yd 3)
Temperature
°C (°F)
Rel. Humidity
(percent)
0.59 (1)
4 (40) 43
1.77 (3)
21 (70) 75
5.93 (10)
38 (100) 98

From the data collected, a statistical regression model was developed to permit prediction of the corrosion rate as a function of these three variables. Even though the model has only a correlation coefficient of 0.50, it serves to demonstrate that, given any chloride concentration, the environmental factors of temperature and humidity also significantly affect the corrosion behavior of steel in concrete. This explains why the problem of reinforcing steel corrosion is considerably more severe in the marine environment of states like Florida than in some other states.

The following are the most important findings resulting from these investigations:

3. Alternative Reinforcements

Even if concrete can be made to be extremely impermeable (by the addition of pozzolans like microsilica, etc.) and not conducive to steel corrosion (by the addition of an effective inhibitor), it still would not completely solve the corrosion problem, since concrete has a tendency to crack eventually, especially the high-performance concrete if proper curing is not observed. The final line of defense against corrosion of reinforcing steel would still lie with the reinforcing steel itself. Unfortunately, the resistance of mild steel to corrosion can not be significantly improved by just modifying its composition, grade, or the level of stress (22). Therefore, to prevent corrosion of steel reinforcement in concrete located in corrosive environment, either the conventional mild steel reinforcement must be coated with an effective and economical barrier to prevent contact with chloride, moisture, and oxygen, or reinforcement made of corrosion-resistant materials must be used.

Among the above two options, application of a suitable coating on the mild steel reinforcement may be the most economical. The coated reinforcing steel must be resistant to damages during transport from a plant to a construction site, storage at construction site, and placement in the structure. It must also be durable in severe service environment and capable of maintaining its structural function throughout the service life of the structure, and be economical.

a. Steel Bars With Organic Coating

After roadway deicing salts was identified as the cause of the premature deterioration of many concrete bridges, solutions to control this problems have to be developed since banning of deicing salts would not be acceptable to the motoring public. A solution that was identified as potentially viable and economical is the application of a suitable, stable organic coating on the reinforcing steel to serve as a barrier for isolating the steel from moisture, chloride ions, and oxygen, thereby preventing corrosion. Therefore, in the early 1970s, the Federal Highway Administration sponsored a project at the National Institute of Standards and Technology, then the National Bureau of Standards, to search for organic coatings suitable for this application. In that study, 47 coatings—including 36 epoxies (in both liquid and powder forms)—were evaluated in the laboratory (23). Four fusion-bonded epoxy powders emerged as the most promising of the coatings studied.

The first bridge utilizing epoxy powder-coated reinforcing steel bars (hereafter called epoxy-coated rebars) was built in 1973 in West Conshohocken, Pennsylvania. Subsequent trial of some of these coatings in bridge decks, under the National Experimental and Evaluation Program, revealed some problems such as damage to the coating during transport and handling, and cracking of coating (in the bend areas) rising from bending of bars at construction sites. To eliminate or alleviate these problems, measures such as bending the bars before coating, increasing bar supports during shipping (to prevent abrasion between bars), and using padded bundling bands and nylon slings during loading and unloading, were adopted.

In a subsequent FHWA study using relatively large concrete slabs, the performance of some epoxy-coated rebars that failed specifications—by having excessive holidays and surface damage (in excess of 0.8 percent) and failing bend tests—was compared with that of black steel (24). It was found that even though the coating on those rebars failed specifications, it was effective in reducing steel corrosion in salted concrete. Based on the data, it was estimated that, relatively, if it required 1 year to consume a given amount of black steel, then 12 years would be required to consume the same amount of the coated rebars, when the epoxy-coated rebars were used only in the top mat bars; or, 46 years would be required, if the coated rebars were used in both top and bottom mats. (The shorter protection accrued when the coated rebars were used only in the top mat was due to the formation of macro-cells between the different types of rebars in the two mats, especially when electrical couplings exist.) It appeared that the presence of the insulating epoxy coating caused significant increase in the electrical resistance between the top- and the bottom-mat of steel bars, which typically behaved as macro-anode and the macro-cathode, thereby retarding steel corrosion.

These findings had lessened the concern that a small exposed area of steel would be susceptible to intense corrosion and, thereby, enabled the requirement for patching or repair of coating damages to be waived when the damage is less than 2 percent in straight bars, 5 percent in bent bars, and 3 percent after placing. This led to decrease in the cost of epoxy-coated steel bars and their wider use in bridges by many states. However, in 1992, a final report for the Canadian Strategic Highway Research Program, "Effectiveness of Epoxy-Coated Reinforcing Steel," raised some questions about the long-term corrosion and structural performances of this type of steel bars, based on observation that some of the epoxy films became disbonded, blistered, and cracked (25). Since then, both ASTM and AASHTO specifications for epoxy-coated rebars, on the presence of holidays and bare area and on coating thickness, were revised and tightened. The Canadian report also urged that the effect of coating adhesion loss on the structural bond and creep properties of concrete members reinforced with epoxy-coated bars be investigated.

To study this important issue, the FHWA conducted a series of short-term experiments to assess the possible effects of disbondment of the epoxy coating from the steel bars on critical bond stress and flexural strength (26). For comparison, a series of pull-out concrete specimens and flexural reinforced concrete slabs were fabricated with: (a) epoxy-coated bars with different levels (20 to 30 percent) of intentionally induced disbondment in coating, (b) epoxy-coated bars with good coating, and (c) black steel bars. Although the investigation was limited in the number of tests conducted and in some other aspects (including bar size, deformation pattern, grade of steel, and slab design used), it was adequately designed to detect any significant differences in the behaviors of concrete fabricated with coating-disbonded bars and normal epoxy-coated bars.

The positive moment tests showed that the mere presence of epoxy coating on the bars, with either well- or partially-bonded coating, appeared to reduce the average ultimate diagonal tension capacity by 14 percent. When the positive-moment flexural behavior of different slabs were compared, no significant difference was observed between bars with partially bonded coating and bars with well bonded epoxy coating. Furthermore, no significant differences were observed in the comparison of the negative-moment flexural behaviors of the concrete slabs cast with the three types of bars. Results from the pull-out tests showed that the critical bond strengths for the bars with partially disbonded coatings were measurably lower than those for good epoxy-coated bars. However, even with 20 to 30 percent coating disbonded, the coated bars still developed 80 percent of the mean critical bond strength for bare bars. Essentially, the study indicated that even with 20- to 30-percent disbondment in the coating, the structural capacity of concrete reinforced with epoxy-coated steel bars was not compromised.

In response to the concerns raised in some portions of the United States, especially in Florida, about potential problem with the long-term durability of present epoxy-coated rebars, a series of investigations were initiated by FHWA in 1993 with the following objectives:

The following are presentation of the various findings resulting from these investigations.

(1) Reexamination of the Performance of Epoxy-Coated Rebars in Concrete Structures Exposed to a Marine Environment.

Following some early success of epoxy-coated rebars in controlling corrosion in bridge decks, some state highway agencies started using them in substructure concrete members in the marine environments, despite some major differences between the exposure conditions existing in bridge deck and marine applications. Reinforced concrete in a marine environment is subjected to:

All these conditions contribute toward lowering the resistivity of the concrete and thereby facilitating the flow of corrosion current between anodes and cathodes in both micro and macro levels.

Therefore, it was not totally surprising when in the late 1980s, reports about the premature deterioration of a number of substructure concrete members in the splash zones of three bridges located in the Florida Keys began to circulate. Even though there were different opinions about the quality of materials and construction practices employed in those bridges, nevertheless it was not expected to encounter in such a short period the severity of corrosion observed. This report led to claims that: (a) when exposed to marine environments, epoxy-coated rebars are more susceptible to corrosion than bare rebars; (b) epoxy coatings are, therefore, not effective in providing long-term protection to rebars in salt-contaminated concrete, even in bridge decks; and (c) the technology of organic-coating of rebars, as practiced in North America, is (probably) flawed. Responding to this concern, a study was initiated to reexamine the effectiveness of epoxy coatings on the steel rebars in substructure bridge members exposed to a simulated marine environment and to identify the cause of the problem, if any (27).

In this study, two parallel sets of experiments were conducted to investigate: (a) anodic growth as a function of immersion time; and (b) cathodic disbondment plus wet-adhesion loss. Quantification of anodic growth was made using (nondestructive) infrared thermography; whereas, quantification of disbondment was made with a specially developed peel test apparatus. The variables included in each experiment were: (a) two commercial epoxy coatings — designated as Coating 1 and Coating 2; (b) two coating thicknesses—approximately 139 and 190 mu(5 to 8 mils); (c) two coating conditions—unscribed and scribed; (d) one immersion solution - saturated Ca(OH) 2solution with 3.5 percent (by wt.) of NaCl; and (e) two immersion-solution temperatures—35°C and 50°C (95°F and 122°F). Approximately 200 steel panels coated with the two coatings were used in the experiments. The following observations were noted:

The basic implication of all these findings is that for epoxy-coated rebars to protect reinforcing steel from corrosion, it's extremely important that the coating is free of any significant damage before being embedded in concrete and special care be observed to avoid damaging the coating during concrete pouring and consolidation. Hence, strict compliance with specifications and use of vibrators equipped with rubber-lined heads were strongly recommended.

(2) Assessment of the Performance of Epoxy-Coated Rebars in Bridge Decks

Recently, 11 state highway agencies in the U. S. and the Canadian SHRP conducted investigations to evaluate the performance of epoxy-coated rebars on 92 bridge decks, 2 bridge baffler walls, and 1 noise barrier wall, which were exposed to harsh service conditions. To shed some light on the controversy regarding the performance of epoxy-coated rebars, FHWA assembled and analyzed the data available from these investigations (28). The bridge decks evaluated included some that were constructed with epoxy-coated rebars used in the top mat of reinforcement only and in both the top and the bottom mats. In addition, 7 different types of epoxy powders were involved in these structures, where the epoxy-coated rebars had been in service up to 20 years at the time of the investigations. In-situ and laboratory evaluations of the concrete and the epoxy-coated rebars were typically included in these investigations. The methodology used in the field or in-situ evaluations included some or all of the following:

The laboratory evaluations used some or all of the following procedures:

The results from the various investigations were summarized according to:

In summary, the following conclusions can be made on the performance of epoxy-coated rebars in the bridge decks surveyed:

(3) Search for New Corrosion-Resistant Organic-Coated Bars

In 1993, following reports of contradictory performances of ECR in piles exposed to marine environment and in bridge decks exposed to deicing salts, FHWA initiated a 5-year research study to develop or identify corrosion resistant rebars that could provide a corrosion-free service life of 75 to 100 years (29,30,31). This study investigated 60 different rebars, including rebars with organic, inorganic, ceramic, and metallic coatings, as well as solid metallic bars.

Among these 60 different rebars were steel bars with 33 different organic coatings, of which 22 were bendable and 11 were non-bendable coatings. The bars were obtained from 15 organizations in the United States, Canada, Japan, England, and Germany. Of these, 17 coatings were utilized in conjunction with new improved steel surface cleaning processes and/or chemical treatments. In addition, since reinforcing bars are typically subjected to various severe conditions during their transportation, storage, installation, and service, the testing was designed to simulate field conditions.

In the Phase I prescreening tests, these rebars were subjected to accelerated solution-immersion screening and cathodic disbonding (CD) tests, using both straight and bent (to 4 D) specimens, each with one 6-mm hole drilled into the coating to simulate severed damage in the coating (29). The adopted test conditions are presented in Table 3. For the immersion tests, four solutions, of different compositions and pHs, were selected to produce corrosion and disbondment that the researchers believed to represent what could be expected during storage at construction sites, installation operations, and in-service behavior within mature concrete (Table 3). The specimens were immersed in these solutions at 55°C for up to 28 days. After immersion for 1, 3, 7, and 28 days the coated bars were visually examined for blisters, cracks, corrosion, and adhesion loss. The adhesion of the coatings was evaluated on both the straight and the bent sections of the bars, using the knofe-peel adhesion tests described in ASTM G1, while the bars were wet and again after 1 and 7 days of air drying.

To assess coating quality, the coating industry has been utilizing cathodic disbondment tests, which are described in AASHTO M284, ASTM A775, ASTM D3963, ASTM G8, and ASTM G42. To make the CD test in this study more severe than similar tests conducted by others, this test was conducted on 4-D bent bars (instead of typically straight bars) to introduce bending stresses on the coatings. As Table 3 indicated, the tests were conducted at a potential of -1,000 mV (versus static potential) over a period of 28 days at 23°C in a solution of 0.3N KOH + 0.05N NaOH at pH 13.3. This solution was used because it had previously been shown to produce more disbondment of organic coatings than other solutions. After 1 hr, 7 days, and 28 days of CD testing, impedance measurements were performed on the specimens; and, coating adhesion evaluation of the specimens was conducted only after the 28-day period.

Table 3. Adopted Test Conditions
Test Solution Immersion Cathodic Disbonding
Specimen Type
(Number)
Straight bars (16)
4-D Bent bars (8)
4-D Bent bars (2)
Solutions
  1. deionized water (pH 7)
  2. 3 % NaCl (pH 7)
  3. 0.3N KOH+0.05N NaOH (pH 13.4)
  4. 0.3N KOH + 0.05N NaOH + 3 % NaCl (pH 13.3)
    All at 55°C (13 1°F)
Same
0.3N KOH + 0.05N NaOH (pH 13.4) at 23°C (73°F)
Duration 1,3,7, and 28 d Same 28 d (at 1000 mV)
Coatings Tested 22 bendable
11 nonbendable
20 bendable
6 nonbendable*
21 bendable
6 nonbendable
* applied on prebent bars

In Phase II, seven of the best performing coatings from Phase I and three other new coatings (the 3M 213 bendable epoxy coating and two non-bendable coatings—an epoxy and a vinyl) were vigorously screened (30). The adhesion of these 10 coating systems on straight, 4D, 6D, and SD bent bars were tested, after solution immersion tests and cathodic disbonding tests, which were conducted under the conditions listed in Table 4.

Table 4. Test Conditions
Test Solution Immersion Cathodic Disbondment
Specimen Type 1. Straight bars
2. 4-D bent bars
3. 6-D bent bars
4. 8-D bent bars
1. Straight bars
2. 4-D bent bars
3. 6-D bent bars
4. 8-D bent bars
Intentional Coating Damage Two 6-mm drilled holes
Replicates 4 per solution 3
Test Solutions
  1. Deionized water
  2. 0.3N KOH+0.05N NaOH
    +9 % NaCl (Cl-/OH- 4.5)
  1. 0.3N KOH+0.05N NaOH (pH 13.3)
Temperature 55°C (131°F) 23°C (73°F)
Potential Shift - -1,000 mV (CSE)
Test Duration 28 days 7 days

The following general observations were made: The last phase of the study was aimed at evaluating the roles that various factors may contribute to the risk of long-term corrosion of epoxy-coated bars in uncracked and cracked concrete. The factors were: reduction in coating adhesion, percentage of coating damage allowed, hole size, bendable versus non-bendable coating technology, and use of steel surface pre-treatments (31).For this evaluation, 6 organic coatings had been selected:

These organic coatings—one from Phase I and five from Phase II—represent a very broad range of adhesion performances. The scotchkote 213 was also chosen since it is in most of the bridges currently in service. For control, a conventional black steel is also included. To more accurately represent real bridge structures, a new and even more severe test method that incorporates a new specimen configuration and cyclic salt ponding is being used. The following is a brief outline of this in-concrete testing of the rebars with the selected coatings:

This in-concrete testing is complete. It is anticipated that analysis of the data and preparation of a report will be completed by the end of 1998 for 75 percent of the concrete slabs. The remaining slabs will be kept for long-term observation.
So far, the following are some of the major conclusions that have been drawn on the performance of ECR in simulated adverse environments in outdoor and indoor laboratory research:

(4) Cost Impact and Potential Pay-Off from Use of Epoxy-Coated Rebars

(a) Cost Impact. For bridge engineers, cost and benefits are always important factors to consider when making materials selection. To illustrate the cost-benefit aspect of using ECR in bridge decks, consider the actual cost data for the construction of three bridge decks recently in Illinois using epoxy-coated rebars in lieu of black steel. The delivered on-site cost of uncoated black steel was $0.44/kg ($0.20/lb) and ECR was $0.62/kg ($0.28/lb). The cost associated with using the different rebars and the total costs of the decks are presented in Table 5. From this example, it is evident that the cost of decks constructed with epoxy-coated rebars averages about 1 percent more than if constructed with black steel.

Table 5. Costs of Bars and Decks
Deck Cost of Bars ($)
Cost of Deck ($)
  Black Steel
Epoxy-Coated
Black Steel
Epoxy-Coated
A
21,644
30,302
690,000
698,658
B
22,544
31,561
880,000
899,017
C
13,614
19,059
1,122,000
1,127,445

(b) Potential Pay-off The potential pay-off can be estimated conservatively on the basis that the ECR deck will provide at least twice the corrosion-free service life of decks built with black steel. On the federal-aid highway system, there are about 2.3 billion square feet of deck surface. So far, ECR has been used on only 100 million square feet of deck. Based upon the average replacement cost of $40/sq. ft. for bridge deck, the potential savings are: $40/sq.ft. x 100,000,000 sq.ft. = $4 billion in 50 years, or earlier. Considering that eventually the remaining decks built with black steel will need replacement, the estimated future savings on the decks will be: $40/sq.ft. x 2,200,000,000 sq.ft. = $88 billion in that same amount of time. Since the above estimated figures are for decks on the federal-aid highway system only, the potential saving is greater if the off-system bridges are also considered in the above scenario.

At present, epoxy-coated rebar is the most common protection system used by 48 state highway agencies. To date, fusion-bonded ECR has been used as the preferred protection system in about 20,000 bridge decks, which represent roughly 95 percent of the new deck construction since the early 1980s. And, the use of ECR has extended to other structures, such as continuously reinforced concrete pavements, parking garages, nuclear power plants, coal plants, aquariums, buildings exposed to the marine environments, and wastewater treatment tanks. At present, there are approximately 100,000 structures containing ECR. Due to the success and the confidence gained by using fusion-bonded ECR over the last 20 years, there are about 35 coating plants. In addition, there are a significant number of people employed in the manufacture of epoxy powders and fabrication of the epoxy-coated reinforcement.

b. Steel Bars with Metallic Coating and Alternative Solid Metal Bars

The success enjoyed by metallic coatings on protecting steel from corrosion in other environments has raised the prospect of similar success in concrete. Metallic coatings that can be applied on reinforcing steel to provide protection against chloride-induced corrosion in concrete can be classified into two categories: sacrificial or non-sacrificial (noble). Coatings made of metal such zinc, which has more negative potentials or less noble than iron, can provide sacrificial protection to steel. When this sacrificial coating on a steel is broken, a galvanic cell or couple is formed whereby the coating is slowly sacrificed. Noble metals such as copper and nickel can also be coated on steel; however, the protection exist only as long as the coating is unbroken, since any exposed steel is anodic to the coating.

Nickel and zinc claddings began to receive attention in the late 1960s and have been shown to be capable of delaying, and in some cases preventing, the corrosion of reinforcing steel in concrete (32,33,34,35). The nickel-clad bar is produced by applying a heavy layer of nickel to a billet before hot rolling to its final form. This results into a continuous surface barrier of wrought nickel, at least 0,025-mm (0.001-in) thick, with an underlying diffusion zone of alloyed nickel and iron, which provides additional corrosion protection in the event of a break in the wrought nickel. The corrosion resistance of nickel is high in alkaline chloride solution, and even if breaks occur in the nickel coating, corrosion of steel is not appreciably accelerated, even though steel is relatively less noble than nickel (32). The results of an 11-year period testing of nickel-coated bars in a marine environment showed that the coating was effective in delaying, or sometime completely preventing, corrosion of the rebars (33). However, steel bars cladded with adequate thickness of nickel are still expensive. In addition, additional research is required to ensure their effectiveness as a corrosion protection system.

(1) Galvanized Rebars

Zinc-coated, or galvanized, bars are produced by a hot-dip process, which consists of cleaning the steel by pickling it and then immersing it in molten zinc. Galvanized bars are typically dipped in a chromate bath to passivate the zinc surface and prevent it from reacting with the hydroxide in fresh concrete. Through this process, zinc is metallurgically bonded to the steel, providing a coating (usually not less than 0.086 mm or 3.4 mils) that is composed of an outer layer of pure zinc and a number of transitional zones of zinc-rich alloys. Since galvanized bars are commercially available, it was the subject of numerous laboratory (32,36,37,38) and field studies (35,39,40). The laboratory results of the performance of galvanized bars in concrete have been conflicting. (Perhaps the conflict pointed to possible influence of experimental techniques on the results and that there is a need to develop an evaluation method that can be standardized.) For example, it was found in one study that when concrete specimens were alternately exposed to 4-percent NaCl in the stressed state, those reinforced with galvanized bars cracked less and later than those reinforced with black steel (38). In another study, data obtained when lollipop concrete specimens were partially immersed in saturated NaCl solution showed corrosion began at roughly the same time for specimens made with galvanized and with black steel, suggesting that there was no benefit from galvanizing the steel bars (36).

A subsequent 10-year FHWA comparative testing of concrete slabs made with two different water-cement ratios and containing either conventional black steel or galvanized bars, wherein corrosion rate was estimated indirectly by measuring macrocell current between top- and bottom-mat bars, indicated that galvanized bars were subject to the same type of macroscopic corrosion as black steel bars (41). Furthermore, in concrete with 0.40 w/c, both the long-term exposure data and the rate-of corrosion data indicated that use of galvanized bars did not provide extra benefit over using black. However, in concrete with 0.50 w/c, when galvanized bars were used in both mats, the corrosion rate and the corresponding metal loss were about 30 percent and 22 percent, respectively, in comparison to black steel. (However, 86-percent reduction in corrosion rate and metal loss was achieved just by using black steel in concrete with 0.40 w/c.) And, in the same concrete, when galvanized bars were used only in the top mat, the corrosion rate was twice of that observed when only black steel was used in both mats. Essentially, these results suggested that the use of galvanized bars would not provide extra benefit over black steel bars, if water-cement ratio in the concrete is kept low. The results also pointed to the possibility of galvanic reaction between galvanized bars and black steel bars, when these bars are used in the same structure.

Field studies of the performance of galvanized bars in concrete structures exposed either to deicing salts or seawater have yielded conflicting results too. For example, accelerated field studies in Michigan over a period of six years have shown that galvanized bars will retard concrete delamination and spalling but will not prevent them, especially where cover over the reinforcement is shallow (42). Meanwhile, evaluation of salt-contaminated bridges that had been in service in Bermuda for up to 20 years noted no corrosion damage (43).

To resolve the discrepancy, a panel made a critical examination of literature on the performance of galvanized rebars from: (a) studies conducted in laboratory environment, (b) studies of model specimens exposed outdoor to either natural or artificial weathering, and (c) studies of reinforced concrete structures under service conditions (44). Briefly, the panel reported that these studies had found that:

Finally, based on the literature and the collective experience of its members, the panel estimated that, for a new concrete bridge deck with a 5.1-cm (2-in.) cover of 0.45 w/c concrete and assuming that normal construction practices are used, the use of galvanized steel bars may add 5 more years to the 10 to 15 years that is typically required for corrosion-induced distress to be manifested in unprotected bridge decks.

(2) Other Cladded Bars and Alternative Solid Metal Bars

With the ultimate goal of developing corrosion resistant reinforcement that will result in a 75- to 100-year design life for concrete structures, The FHWA sponsored a 5-year research project to evaluate corrosion-resistant bars. As part of that project, 24 different bars of various types were tested with newly developed accelerated tests that are considered to be more severe than most available test procedures and much more severe than typical field conditions (45). The 24 bars included 14 ceramic-, inorganic-, and metallic-clad bars:

(2) Ceramic-clad bars (using a micro-infiltrated macro-laminated coating),
(1) Inorganic zinc silicate-clad bar,
(1) Hot-dip galvanized bar,
(1) Zinc coated bar (using the Delot process),
(3) Zinc-rich cladded bars,
(1) Nickel-clad bar,
(1) Copper-clad bar,
(1) Copper alloy-clad bar,
(1) 304 stainless steel-clad bar,
(1) Galvalum (aluminum and zinc) clad bar,
(1) Reactive copper in an organic coating bar,

and 10 different types of solid metallic bars:

(1) Black bar,
(1) Titanium bar,
(1) Type 304 stainless steel bar,
(1) Type 316 stainless steel bar,
(1) Type 317 stainless steel bar,
(1) Type 304N stainless steel bar,
(1) Type XM-19 stainless steel bar,
(1) Nitronic 33 stainless steel bar,
(1) Corrosion-resistant steel alloy bar,
(1) Type C613000 aluminum bronze bar.

Initially, the 14 cladded bars, in both straight and bent forms, were tested for 28 days (in 112 cycles of 1.25 hours dipping in specified solutions and 4.75 hours drying in air) in two solutions (a 3-percent NaCl solution, which has a pH 7, and a solution of 0.3N KOH + 0.05N NaOH + 3-percent NaCl, which has a pH of 13). Both straight and bent bars were tested in three conditions: (1) as received, (2) with a 6-mm (0.25-in) hole intentionally drilled through the cladding, and (3) with cladding purposely abraded with black slag sprayed on the bars at a specified distance and then pressured for 5 minutes. Based on the polarization resistant data, along with visual examination of the condition of these 14 different cladded bars after 28 days of testing in the two solutions, the following five cladded bars were selected for additional testing:

These five cladded bars, along with the above-mentioned 10 different solid metallic bars, were further tested for longer periods and under more severe conditions. The very corrosive solutions and severe exposure conditions used sequentially in this test are tabulated in Table 6.

Table 6. Corrosive Solutions and Exposure Conditions

Test Order
Test Solutions
Test Duration
1
3 % NaCl (pH 7)
90 days
(360 cycles)
2
3 % NaCl + 0.3N KOH + 0.05N NaOH (pH 13)
56 days
(224 cycles)
3
9 % NaCI + 0.3N KOH + 0.05N NaOH (pH 13)
56 days
(224 cycles)
4
15 % NaCl + 0.3N KOH + 0.05N NaOH (pH 13)
56 days
(224 cycles)

The 3-percent NaCl solution was selected to provide the exposure to seawater that may be encountered by bars prior to installation into the concrete or at cracks after placement in concrete. So, after 90 days of exposure to this solution, the bars are subjected to a total of 168 days of additional exposure to the three more-severe solutions, thereby providing a total of 1,032 wet-and-dry cycles.

The measurements indicated that the polarization resistance of the black bars in the various NaCl solutions (at pH 13) averaged about 0.90, 0.51, and 0.26 ohm·m 2, respectively. These correspond to corrosion current densities of approximately 29, 50, and 100 mAm 2 (2.7, 4.7, and 9.3 mA/ft 2), respectively. Assuming that concrete cracking occurs after a metal loss of 0.0254 mm (0.001 in), the calculated metal losses for the current densities observed for the black bars at 56 to 168 day (d) accelerated tests indicated that the concrete could crack in 1 year or less.

Using the same assumption, the approximate time-to-cracking for concrete using the various reinforcements were predicted and shown in Table 7. And, based on review of the polarization resistance data and visual assessment for the 15 types of bars, the 10 best performing bars were determined to be: the 7 solid stainless steel bars, the stainless steel-clad bar, the aluminum bronze bar, and the titanium bar. However, after consideration of cost and other factors (including availability), only 4 bars were selected for additional testing, with 6 different epoxy-coated bars identified earlier. These 4 bars were the Type 304 stainless steel bars, the copper-clad bar, the galvanized bar, and a zinc alloy-clad bar (with a newer zinc alloy).

Table 7. Time-to-Cracking
Type of Bars Time-to-Cracking
Zinc-clad slightly better or worse than black bars
Zinc alloy-clad bars slightly better or worse than black bars
Copper-clad bars @ 5 years
Stainless steel-clad bars 23 to 50 years
Nitronic 33 bars @ 100 years
Type 304 stainless steel bars
@ 100 years
I Type 316 sainless steel bars @ 100 years
Titanium bars @ 100 years

The 10 different bars and an ASTM A615 black bar (control), in both straight and bent shapes, were embedded in cracked and crack-free concrete test specimens of 9 varied test configurations, then subjected to in-concrete tests (46). As mentioned earlier, the final report for this ongoing research will be available by December 1998.

(3) Cost Comparison Between Black Steel, Epoxy-Coated, Stainless Steel, and Titanium Bars

As mentioned in an earlier section, selection of materials is usually based on performance and cost. To demonstrate that replacing black steel bars with the more expensive stainless steel bars may not be that significantly more costly, FHWA researchers used the actual 1994 costs associated with the delivered on-site costs of black steel and epoxy-coated steel bars at three bridge projects in Illinois, which were $0.44/kg ($0.20/lb) and $0.62/kg ($0.28/lb), respectively. And, according to industrial sources, the corresponding prices for stainless steel and titanium bars were approximately $2.60/kg ($1.20/lb) and $13.20/kg($6.00/lb), respectively. Based on these costs and the bid prices for the three bridges, the overall costs (including site work and finishing) of the three bridges for using stainless steel and titanium bars instead were estimated (Table 8). When these costs were compared with those bid prices for using black steel bars or epoxy-coated bars, it showed that use of stainless steel bars would have increased the initial total project costs by only 6 to 16 percent; while use of titanium bars would have increased the initial costs by 35 to 91 percent. Considering that use of stainless steel rebars in these bridges may increase the time-to-cracking of a concrete by 65 to 130 times, in comparison to black steel and based on data obtained from ongoing tests of these different bars in the pH 13 solution, the benefit-to-added cost ratios would have to be considered very favorable (47). Similar test data for the titanium bars indicated that its use would extend the time-to-cracking of concrete by approximately 130 times, which would not provide a benefit-to-added cost ratio as attractive as that for using stainless steel bars.

Table 8. Cost Comparison
  Cost of Rebar /
Cost of Black Bar
Total Cost with Rebar /
Total Cost with Black Bar
Bridge A
Bridge B
Bridge C
Black steel 1.0 1.00 1.00 1.00
Epoxy-coated 1.4 1.01 1.02 1.00
Stainless steel 6.0 1.16 1.13 1.06
Titanium 30.0 1.91 1.74 1.35

(4) Copper-Clad Steel Bars

Copper-clad reinforcing steel bar is another of the metallic coated bars that were recently selected for additional evaluation. This type of reinforcing bars was initially tested in concrete in 1980 and 1984. In 1980, FHWA fabricated an extensive series of large test concrete slabs that contained various types of reinforcement—including black steel bars (in concrete with and without admixed calcium nitrite), non specification epoxy-coated bars, and copper-clad bars—and had various amounts of chloride added to the top lift of concrete. Since then, these slabs have been inspected several times (48). The conditions of these slabs at different ages are shown in Table 9.

Table 9. Slab Conditions
Slab Type Age of the Slabs (years)
2 7 13
Black bars Badly cracked and
bars corroded
----- -----
Black bars and calcium nitrite No cracks, but
minor rust spots
Fine to wide cracks
and some spalls
-----
Nonspecification epoxy-coated bars* No cracks Cracked and bars
corroded
-----
Copper-clad rods—
in both mats
----- ----- No cracking
Copper-clad rods—
in top mat
----- ----- No cracking
Black bars ----- Severe cracking Severe
cracking
* Containing uncountable holidays and less than 0.80-percent damage in coating.

As the inspection results indicated, the copper-clad bars were far more resistant to corrosion than any of the other types of bars in the identical test concrete slabs, and providing protection even better than calcium nitrite inhibitor. The slabs containing black bars started to crack severely after 2 to 7 years, even when the concrete had calcium nitrite. The slab reinforced with an epoxy-coated bar that had uncountable holidays and less than 0.80-percent damage performed better, but finally showed symptoms of corrosion after 7 years. The slabs containing copper-clad bars in both mats and in top mat only, were still in good condition after more than 13 years of outdoor exposure. It must be noted that the average total chloride contents in the slabs containing the copper-clad bars were between 8.50 to 10.32 kg/m 3 (14.33 to 17.40 lb/yd 3), which is at least 14 times of the corrosion threshold level. Examination of cores taken from these two slabs revealed that the cladded bars, with cladding thickness of about 0.5 mm (0.02 in.), had discolored the surrounding concrete to a gray-green color. Petrographic examinations indicated that there was significantly higher amount of unhydrated cement around the copper-clad bars—extending 0.25 to 0.5 mm (0.01 to 0.02 in.) into the concrete—than at other locations. It is well known that copper, lead, and zinc salts can be retard hydration of cement. Despite the presence of unhydrated cement, the cement paste surrounding the bar appeared to be sufficiently hard in the concrete.

These findings correlated well with the results from an earlier 1984 study, which involved 48-week cyclic wetting (in 15-percent sodium chloride solution) and drying tests of concrete specimens reinforced with copper-clad bars. The copper-clad bars showed similar good corrosion resistance—during the 48-week ponding test, none of the specimens that contained the copper-clad bars exhibited signs of chloride-induced corrosion activity. Similar to the 1980 study with the same type of bars, discoloration of the concrete and retardation of cement hydration in concrete surrounding the copper-clad bars were observed at the end of the testing. In addition, the copper cladding was generally blackish in color—probably the normal copper oxide film formed after the fabrication of the specimen.

Due to the exceptional corrosion resistance shown by copper-clad bars in these studies, along with successful performance of these bars in the recent 168-day screening tests that was described earlier, it was decided that these bars should be tested further in concrete. These tests, as mentioned earlier, are under way and the results will be available in December 1998. It is clear that this type of reinforcing bar has the potential of becoming a cost-effective option for corrosion protection system, since the cost of copper-clad bars could be under $1.20/kg ($0.54/lb). However, further study on the structural effect of the retardation of cement hydration is required, prior to using such bars in bridge structures.

4. Corrosion Inhibiting Admixtures

In the past decade, a promising new approach to controlling steel corrosion in concrete structures is the incorporation of a corrosion inhibitor in the concrete mixes. Corrosion inhibitors are materials, both inorganic and organic, that are added to water or other liquids or gases in small amounts to reduce or completely stop corrosion. Inhibitors have been classified in many ways, including by composition and mechanism of action. Substances that retard corrosion by forming protective precipitates or by removing an aggressive constituent from the environment are also considered as inhibitors. The mechanism of inhibition is often complex and varies according to the type of inhibitors. For simplicity, the major inhibitor classifications are:

With the widely marketed calcium nitrite, inhibition occurs only at addition dosage that is sufficiently high to counteract the effect of chlorides. In addition, this inhibitor is water-soluble and is, therefore, subject to leaching from concrete and hence would become less effective after some time. Some of the inhibitors may cause adverse effects in concrete, such as low concrete strength, erratic setting times, efflorescence, and enhanced susceptibility to alkali aggregate reaction. Finally, the real long-term benefit provided by these materials in concrete - the commercial corrosion inhibitors in particular - remains uncertain. Despite the risks and uncertainty, the use of corrosion inhibitors, both inorganic and organic, as admixtures for the corrosion protection of steel in reinforced and prestressed concrete has increased in the last fifteen years. A recent survey (49) indicated that, at present, there are four commercial corrosion inhibiting admixtures. These are:

The bulk of the performance data for these corrosion inhibiting admixtures are obtained mostly from laboratory tests conducted by their manufacturers - using simulated environment and/or small concrete specimens; the rest come from investigations conducted by FHWA, some of the state transportation agencies, and the academia. Most of these data pertain to DCI, because this commercial inhibitor was introduced in 1978 while the others were introduced in the last five years. Due to the long time required to assess their performance and the lack of follow-up studies once a structure is built, field performance data on any of these admixtures are still very limited. Therefore, it is not yet possible to accurately define the actual benefits that can be expected from the use of a specific corrosion inhibiting admixture other than to state that delay of corrosion initiation is anticipated.

Investigations of the use of corrosion inhibitors in concrete started in the 1960s and included sodium nitrite, and the sodium and potassium salts of chromate and benzoate. It was found that the sodium and potassium salts of chromate and benzoate gave mixed results on inhibition and reduced concrete strength. In one early study, it was shown that nitrite and chromate were effective inhibitors (51). A subsequent study indicated that only sodium nitrite was effective but it exhibited deleterious effects on the strength of the concrete (52). In the late 1970s, calcium nitrite was introduced commercially as an alternate form of nitrite (53).

In 1980, the FHWA began an outdoor exposure study to assess the effectiveness of calcium nitrite as an admixture for inhibiting steel corrosion in concrete (54). Eighteen reinforced concrete slabs (0.6 m x 1.52 m x 0.15 m) were built to simulate bridge decks using bared black steel bars. Of these slabs, 13 slabs contained various amount of admixed chloride and 2.75-percent calcium nitrite (by weight of cement) in the top lift and 5 control slabs without admixed nitrite. These slabs were tested by periodic measurements of macro-cell corrosion current, half cell potential, driving voltage (i.e., potential difference between the top- and bottom mat reinforcing steel), and concrete electrical resistivity (i.e., resistance between the top and bottom mats), as well as visual inspection. Based on data at the time, it was concluded that:

However, after testing of the same 18 concrete slabs were continued for 7 years, it was found that calcium nitrite was effective in reducing the rate of corrosion of black steel up to a [Cl -] /[NO -] of only 0.90, instead of the higher [Cl -] /[NO -] of 1.79 indicated earlier (55). In fact, the slabs fabricated with higher ratios, even up to only 1.11, showed some cracking and rust spots on their surfaces after 7 years, despite exhibiting a reduction in corrosion current by a factor of 10. Since the chloride and the nitrite were added at the same time when the test slabs were being fabricated, it is reasonable to assume that a [Cl -] / [NO -] higher than 1 may still be able to suppress steel corrosion, if the chloride ions penetrates instead naturally into the concrete as in a structure. However, the researcher still recommended that, if selected as the protection system in a new construction, sufficient quantity of calcium nitrite should be added to the fresh concrete mix so that the [Cl -] / [NO -] will not exceed 1.0 at the level of steel—throughout the expected design life of a structure.

Recently, several new inhibitors and the first three commercial inhibitor admixtures were examined in a preliminary study of inhibitors conducted in Virginia (56). Using electrochemical impedance spectroscopy and visual observation, the investigators measured and ranked the overall inhibition performance of these inhibitors in simulated pore solution. It was determined that the top three inhibitors were barium metaborate, disodium beta-glycerophosphate, and one of the commercial inhibitors. A follow-up study is under way to allow: (a) additional testing of these inhibitors in concrete to determine if their use has any adverse effects on setting and other properties of concrete, (b) development of an unique method of inhibitor delivery for alleviating such adverse effects, if there is any, and (c) expansion of the search to other new inhibitors (57). Another study is under way in Florida to (a) evaluate the ability of commercial inhibitors to stay in the concrete, which would influence their effectiveness, (b) estimate the long-term effectiveness of inhibitors, (c) determine possible adverse side effects on the corrosion process and the concrete properties, (d) quantitatively assess extension of concrete durability, and (e) establish their suitability for applications in new construction and in rehabilitation (58).

Recently, the commercial inhibitors—particularly the first three products—have been promoted for use in repair of corrosion-damaged concrete in bridges, either by: (a) addition as admixture to patching concrete, (b) spray application onto affected areas, or (c) saturation treatment to affected areas. Unfortunately, data on the effectiveness of this approach of using inhibitors are relatively limited. Therefore, an on-going study in Virginia is attempting to develop some data from actual bridge rehabilitation projects and concrete slabs fabricated to simulate bridge situations for assessing the effectiveness of these commercial inhibitors when used in rehabilitation (59).

Due to lack of widely accepted standard evaluation test that can truly be applied to all types of inhibitors, regardless of their inhibition mechanisms, comparison of the effectiveness of different inhibiting admixtures present difficult challenges. It's likely that a system of different acceptable tests would have to be developed. Furthermore, the effectiveness of all inhibitors should be evaluated based on per unit weight of the active ingredient(s) - the commercial corrosion inhibiting admixtures in particular. Unfortunately, most of the manufacturers are reluctant to share information on the compositions, or even just the concentrations of the active ingredients, of their products with the users.

In summary, corrosion inhibitors are increasingly being employed as a part of multiple corrosion protection systems in conjunction with epoxy-coated rebars and low-permeability concrete. As yet, epoxy-coated seven-wire strands are not usually employed for prestressed concrete bridge members. In lieu of coated seven-wire strands, corrosion inhibitors have found their niche in the prestressed highway construction industry. In addition, corrosion inhibitors are finding use in cementitious grouts for filling the post-tensioning ducts of bridge members or the sheating of cable stays to protect the highly tensioned and uncoated black steel. Due to the premature failure of epoxy-coated rebars in the splash zone of piles on the Florida Keys bridges, some state highway agencies are relying on corrosion inhibitors as one of the alternative corrosion protection systems for marine application. For bridge deck exposed to excessively aggressive environment, the use of a corrosion inhibitor, in conjunction with ECR, as a redundant corrosion protection system, can enhance the service life of a structure with respect to corrosion. (Industry-sponsored research is under way on the combined use of ECR and corrosion inhibitors as a dual corrosion-protection system for bridge decks.) In addition, the corrosion inhibitors can play an important role in protecting uncoated high-strength steel in PS/C bridge members and cable-stayed bridges. Research is continuing to identify other corrosion inhibitors that will provide long lasting corrosion protection to bridge members.

5. Corrosion Protection of Prestressed Concrete Bridge Members

In the fall of 1992, the United Kingdom Ministry of Transportation imposed a temporary ban on the commissioning of grouted, bonded post-tensioned bridges. This resulted from the collapse of two footbridges in 1960, the collapse of a single-span, segmental post-tensioned bridge in Wales in 1985, and an examination of nine other segmental bridges. United Kingdom is not the only place with problems of voided ducts and insufficient coverage over prestressing steel in ducts, as evident by the collapse in 1992 of the post-tensioned Melle Bridge across the Schelde in Belgium, which was constructed in 1956. This last failure was traced to the corrosion of the ducted post-tensioning wires even though the bridge had been inspected, load tested, and rated satisfactorily. The UK moratorium was lifted in 1996 with the publication of advisory report "Post tensioned Concrete Bridges: Planning Organization and Methods for Carrying Out Special Inspections" by the construction industry and owners of this type of bridges.

The underlying difficulty is that there are no reliable, cost-effective, and rapid nondestructive methods for providing assurance to the owners that the built structures have met the construction specification. One of the major inspection concern is determining whether the ducts in the post-tensioned bridge members have been completely filled with the grouts and that there is uniform coverage over the prestressing steel. It has been found many times that, invariably, the ducts had big voided sections and were filled only partially. In addition, it is very difficult to assess the condition of anchorage areas.

Chloride-bearing water can find its way through anchorage into the ducts and eventually initiate corrosion at the anchorage and subsequently of the prestressing steel inside the ducts, especially if the ducts have voids and are partially filled. The salty water can also access the ducts through faulty and leaky joints. In time, the chloride ions also penetrate through concrete cover and corrode the prestressing steel in the ducts, either after the corrosion of the metallic ducts or through defective plastic ducts. Beside causing pitting of the prestressed strands, corrosion reactions lead to the evolution of atomic hydrogen, which is subsequently absorbed into the steel leading to hydrogen embrittlement of the steel. This embrittlement can cause the strands to fail much more readily under normal loads. Since prestressed concrete bridge members rely on the tensile strength of the strands to resist loads, loss of even few strands per member can prove catastrophic. In addition, due to the high stresses the strands are subjected to, corrosion effects are accelerated. Even though corrosion initiate on prestressed steel in the same manner as on mild reinforcing steel, there is one significant difference between the two: since prestressed wires have smaller cross sections than rebars, sections of prestressed wires are more readily broken or completely rusted away.

Corrosion protection methods adopted at present in the construction of prestressed concrete members included: (1) the use of highly impermeable concrete through the use of fly ash and silica fume and controlled curing at the fabrication site, and (2) the use of corrosion inhibitor admixtures. The use of epoxy-coated steel is not yet common in prestressed concrete members and research on this application of coated strands is needed.

The main thrust of FHWA field and laboratory investigations in this area of prestressed concrete consisted of the following:

a. Field Investigations

Many problems associated with deterioration of prestressed concrete members can be traced to improper designs in a structure. To help identify some common examples of improper design, a total of 17 prestressed concrete bridges were surveyed between 1988 and 1992 and the collected data were analyzed (60,61). Built between 1954 to 1979, eleven of these bridges were pre-tensioned and six were post-tensioned—with some of the bridges containing both types of members. These bridges were located both in northern climates exposed to application of roadway deicing salts and in southern climates exposed to seawater spray. The procedures used in the examination included: visual examination, concrete delamination survey, chloride content survey, concrete cover survey, half-cell potential survey, rapid chloride permeability, and petrographic and metallurgical analysis of the prestressed steel.

The detailed examinations of these bridges revealed that, since most common sources of chlorides in concrete in the substructures are water running from bridge decks and spray from seawater, the corrosion of prestressed steel observed in these bridges was due commonly to one or more of the following causes:

Overall, the conditions of the bridges surveyed were judged to be adequate. And, to add to the durability of these types of concrete structures located in adverse environments, the following recommendations were made for:

Finally, the researchers emphasized that routine inspection and proper maintenance are extremely important in eliminating major deck-to-steel water routes for prestressed substructure concrete elements.

b. Laboratory Investigation

(1) Corrosion-Resistant Grouts

Grout is the final line of defense against corrosion of steel tendons. Based on review of state highway agencies' specifications on grouts, it was determined that the design mixtures were inadequate and that there was no suitable method for evaluating the corrosion performance of grouts before their use in the field. Hence a study was initiated with the following objectives: (1) to develop new mixture designs, and (2) to develop and perform accelerated test methods on the new grouts. In this study, in addition to varying w/c, several modifiers and additives for grouts were examined, including high-range water reducers, fly ash, silica fume, latex-polymer modifier, expansive agents, anti-bleed additives, and corrosion inhibitors (62,63,64,65,66).

A large number of grout design mixtures were tested with an accelerated corrosion test method (ACTM). ACTM uses a test specimen that simulates a post-tensioning strand embedded in grout, but with a section of duct missing (representing a break in the duct). Other features of the test included minimal cover on the tendons, a 5-percent sodium chloride solution in direct contact with the grout, and forcing of chloride ions through the grout by an applied voltage. The study resulted in the following conclusions:

In summary, use of fly ash or silica fume, in conjunction with proper dosage of a corrosion inhibitor with a suitable anti-bleeding agent, can provide a grout which can protect the prestressing steel even if it is contained in defective ducts. Based on these recommendations, the Post-Tensioning Institute has written a grouting specification, which will be published in 1998.

(2) Inspection of Grout Cover Over Prestressing Steel and Voids in the Ducts

Prior to the discovery of problems with grouting of ducts in existing prestress sing concrete structures in UK and other parts of the world, little attention was given to this subject. Review of literature offered the following relevant techniques:

Neither of these techniques are widely used in the United States, if at all, because the first two are destructive and the third technique, even though it is nondestructive, involves a bulky equipment and is expensive. Hence, FHWA initiated a research study to develop an equipment which is in the range of $15,000 to $25,000 and also not bulky. After completion of the first phase of this study, the impact-echo technique was selected for further evaluation and development, since it showed the most promise (66,67).

In this method, a short-duration stress pulse is sent through the duct location under inspection by striking the outer concrete surface. The reflected pulses are received by a transducer (which is in close proximity to the impactor) and is displayed on a computer screen as a frequency spectrum. The frequencies of the pulses reflected from a voided and/or partially filled duct are much lower than those reflected from a filled duct. This technique has been successfully used on a few bridges. The concrete cores taken from the suspected locations showing lower frequency had either a void in the duct or honeycombing around duct area. The correlation between the nondestructive impact-echo technique and the destructive examination of concrete cores was excellent.

B. Corrosion Control for Rehabilitation of Existing Concrete Structures

There are different remedial methods that can be applied, as part of rehabilitation of existing concrete structures, for controlling chloride-induced reinforcing steel corrosion. Each of the methods, which are used after all damaged concrete in a structure have been removed and patched, functions by one of the following principles:

1. Conventional Rehabilitation Methods

Methods that function by the first approach—such as application of an overlay of polymer concrete, low slump concrete, latex modified concrete, or high density concrete, on the existing concrete—provide a barrier that prevents continued intrusion of additional harmful chloride ions, moisture, and oxygen that are needed to sustain corrosion. In some cases, these methods have successfully extended the useful life of a structure. However, past experiences have also indicated that when such measures were used, without first decontaminating the existing concrete of the necessary corrosion ingredients, it was often that these substances become entrapped (in the old concrete) by the overlays in sufficient amounts to initiate new corrosion. Furthermore, the ensuing corrosion is often worse than before rehabilitation, due to arising electrochemical incompatibility between the new patching concrete and the surrounding old but physically sound concrete (68). The following is a brief summary of work performed on measures belonging to approach one.

FHWA undertook a long-term staff study in the 1980s to evaluate the effect of various conventional repair systems on the rate of corrosion of reinforcing steel (69). It had been debated whether the overlaying of a bridge deck with a relatively impermeable concrete or membrane would sufficiently arrest the corrosion to effect a permanent repair. The following overlays were placed on chloride-contaminated reinforced concrete slabs and tested:

The concrete specimens were 1.2-m-wide x 1.5-m-long x 0.152-m-thick (4-ft. x 5-ft. x 0.5-ft.) slabs that were fabricated in 1971 using a top-mat reinforcing steel only. These slabs were subjected to daily salting for 8 years. All of the slabs in this phase of the study were fabricated using concrete with a 0.5 w/c and 25.4 mm (1.0 in) of clear concrete cover over the reinforcing steel, and exhibited some corrosion-induced concrete distress. Measured electrical potentials indicated the presence of corrosion on the rebars in all slabs. In order to make the slabs more closely simulate a bridge deck, a 63.5-mm (2.5-in) layer of chloride-free concrete containing a mat of reinforcing steel was placed on the bottom of each slab. Prior to concrete placement, the old bottom of each slab was sandblasted to exposed coarse aggregate. Care was exercised to insure the new bottom mat of steel was not electrically continuous to the top